DZ47 (C45N) Mini Circuit Breaker

DZ47 (C45N) series circuit breaker is used in lighting distrbution system or motor distribution system for portecting overload and short-circuit in the system. The product is novel in structure, light in weight, reliable and excellent in performance. It has high breaking capacity, can trip quickly and its easy installation uses with guide. Its case and items are adopted by high fire-resistant and shockproof plastics. This product, with long life, is mainly used in AC 50Hz/60Hz single-pole 240V or two, three, four-pole 415V circuit for overload and short-circuit protecion as well as for unfrequent on-and-off switching of electric equipment and lighting circuit under normal condition. The products comply with IEC 898 & BS 3871.

Setting temperature of protective characteristics at 40

Rated Voltage: 240V/415V

Rated Current: 1,3,5,10,15,20,25,32,40,50,60A

Electrical life: no less than 6000 operations

Mechanical life: (O-C) no less than 20000 operations



Specifications

DZ47 (C45N)

Standard

BS 3871-1

IEC898

IEC 157-1

Rated current (A)

1 to 40

50 to 60

50 to 60

1

3

10 to 40

50

60

Pole No.

1

2 3 4

1

2 3 4

1

2 3 4

2 3 4

1

2 3 4

2 3 4

1

2 3 4

2 3 4

1

2 3 4

2 3 4

1

2 3 4

2 3 4

Voltage (V)

240

415

240

415

220

240

220

240

380

415

220

240

220

240

380

415

220

240

220

240

380

410

220

240

220

240

380

410

220

240

220

240

380

410

Breaking capacity (A)

6000

6000

4000

4000

1000

2000

1000

8000

2000

8000

7000

16000

8000

6000

10000

6000

5000

10000

5000

 

BHP  Mini Circuit Breaker

     BHP series miniature circuit breaker has small size, light weight, novel structure and excellent performance. They are mounted in the illuminating distribution board and used in guesthouses, block of flats, high buildings, squares, airports, railway stations, plants and enterprises etc, in AC circuits 240V(single pole) up to 415V (3pole)50Hz for protection of overload, short circuit and for circuit change-over in lighting system. Breaking capacity is 3 KA. The items comply with BS & NEMA standard.

Specifications

Rated Current (A)

Poles No

(P)

Rated Voltage

(V)

Breaking capacity (KA)

Setting temperature of protective characteristics

B.S

NEMA

6,10,15,

20,30,

40,50,60

1P

2P

AC12

 

5

40

AC120/240

 

5

AC240/415

3

 
 

AC120/240

   

40

AC240/415

3

5

3P

AC240/415

3

 

BHP-S M6

6

40

 

S060 Mini Circuit Breaker

The products are suitable for overload and short circuit protection in the circuit of AC 50/60Hz, rated voltage of single pole up to 240V, two or three poles up to 415V and rated currdnt up to 60A. It can also be used for and unfrequent switchover of the circuit and illumination under normal condition.

Specifications

Rated Frequency

50/60Hz

Rated Voltage

240/415V AC

Rated Breaking capacity

300A

Rated Frame Current

40A

Rated Trip Current

2,4,6,10,20,25,32,40A

Pole No.

1P,2P,3P,

 

W40 Mini Circuit Brealer

W40 series miniature circuit breaker has characteristics of small size, light weight, novel structure and excellent performance. They are mounted in the illumination board and used in guesthouses, block of flats high buildings, squares, airports, railway stations, plants and enterprises etc, in AC circuits 240V (single-pole), up to 415V (2,3-pole) 50Hz for overload and short circuit protection and for circuit changeover in lighting system. Breaking capacity is 3KA.

Its indicator can be used as circuit indication in illumination and industry system.

 Specifications

Rated Current (A)

1,3,6,10,16,20,25,32,40A

Rated Voltage (V)

240/415V AC

Breaking Capacity (A)

3000A

Machanical life (times)

10000

Specifications

Tripping characteristic

Rated tripping current (A)

Thermal trip

Magnetic trip

Time of rated tripping current

G1-G32

1-32

1.13ln

1.45ln

2.55ln

3ln

5ln

Starting state

From

cold state

From warm state

From cold state

From cold state

From

cold state

Tripping time

1hr,.

1hr,.

lsecT60sec.

0.1sec.

0.1sec.

Specifications

Tripping characteristic

Rated tripping current (A)

Thermal trip

Magnetic trip

Time of rated tripping current

L1-L32

1-32

1.13ln

1.45ln

2.55ln

3ln

5ln

Starting state

From

cold state

From warm state

From cold state

From cold state

From

cold state

Tripping time

1hr,.

1hr,.

lsecT60sec.

0.1sec.

0.1sec.

 

C60N Mini Circuit Breaker

C60N mini circuit breaker belongs to the advanced level of the nineties in the world instead of the old generation of C45N.  They have protective functions as short-circuit and overload, and are used in lighting distribution system in industry, commerce and dwelling, and to protect fractional electric motors. And they also have many merits of high protective grade (up to IP20), high breaking capacity, good reliability, sensitive action, convenient multi-pole assorting, long using life etc. They are mainly adapted to the circuit of AC 50Hz,230V in single pole, 400V in double, three, four poles for protecting overload and short circuit. Meanwhile, they are also used in turning on or off the electric apparatus and lighting circuit under the normal condition.

Specifications

Character

Standard

Rated current

(A)

Pole No.

Rated Voltage

(V)

Breaking capacity (A)

B

C

D

IEC-898

1,2,3,4,5,6,10,16,20,25,32,40,50,63

1

230/240

6000

2,3,4

400/415

6000

IEC-947-2

1,2,3,4,5,6,

10,16,20,

25,32,40,50,

63A

1

130

20000

230/240

10000

400/415

3000

2,3,4

230/240

20000

400/415

10000

440

6000

S101 Screw Circuit Breaker

The circuit breakers are suitable used in AC and DC 32A and below electric circuit of 50Hz, up to 380V and to DC 250V respectively, for protection of electric circuits and apparatus in office and residence buildings, and for protection of circuit terminals against overload and short circuit. The item is a durable protection that substitutes the traditional fuse element and can be used in each fuse socket with E27 thread according to DIN40440.

Specifications

Rated current (A)

2.25A

32A

Pole No.

Single pole

Single pole

Rated voltage (V)

250/380V

250/380V

Rated short-circuit

making capacity

Prospective current in testing circuit (A)

3000

3000

Power factor of

testing circuit

0.65-0.70

0.75-0.80

 

NFIN Earth Leakage Circuit Breaker

The earth leakage circuit breaks (RCB)NFIN is in conformity with the standards of VDE 0664, CEE 27 and BS 4293.

It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth leakage.

NFIN RCB is mainly suitable for using in variety of plants, enterprises, buildings, constructions, commerce, guesthouses and families. It can be used in circuits up to single phase 240V, three phase 415V, 50Hz or 60Hz.

Specifications

Type

NFIN25

NFIN40

NFIN63

Rated current in (A)

25

40

63

Rated operating current for earth leakage lΔn (A)

0.03, 0.1, 0.3, 0.5

Rated non-operating current for earth leakage lΔn (A)

0.51Δn

Voltage Un (V)

240 (220)   415 (380)

Pole No.

2

4

  The earth leakage circuit breakers type FIN is in conformity with the standards of VDE 0664, CEE 27 and BS 4293.

It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line. Thus it is suitable to avoid the shock hazard and fire caused by earth leakage.

NFIN ELCB is mainly suitable for using in variety of plants, enterprises, buildings, constructions, commerce, guesthouses and families. It can be used in circuits up to single phase 240V, three phase 415V, 50Hz or 60Hz.

Specifications

Type

NFIN25

NFIN40

NFIN63

Rated current in (A)

25

40

63

Rated operating current for earth leakage lΔn (A)

0.03, 0.1, 0.3, 0.5

Rated non-operating current for earth leakage lΔn (A)

0.51Δn

Voltage Un (V)

240 (220)   415 (380)

Pole No.

2

3

4

DZ47L (C45L) Earth Leakage Circuit Breaker

C45L earth leakage circuit breakers are used for the protection against electrical leakage in the circuit of 50Hz or 60Hz, rated voltage single-phase 240V, 3 phase 415V, rated current up to 60A.When somebody gets an electric shock or the residual current of the circuit exceeding the fixed value, the ELCB can cut off the power within the time of 0.1s automatically for protecting the personal safety and preventing the equipment from the fault resulted by the residual current .With this function, the ELCB can protect the circuit against over-load and shortcircuit or can be used for the unfrequent switchover of the circuit under normal conditions. It conforms to IEC898-87 & IEC755.

Specifications

Rated Voltage (V)

Pole No.

Rated Current (A)

Leakage action current (mA)

Leakage dead current (mA)

Leakage action time (s)

 

220

1P

1~10

30

15

0.1

15~32

380

1, 2, 3P

100

50

40~60

M611 Motor Protection Circuit Breaker



This product is suitable for using in circuit up to AC 660V or 400Vand current 0.1 to 16A. It can be used for protection of overload and short circuit of 3-phase squirrelcage motors, and starters of motors as well at full voltage. It is suitable to be used to protect the motor with under voltage. It can also be used in operating AC single phase load and DC load, to monitor the fuse of switch disconnector to act as protection of phase failure.

This product includes basic type switch and 26 accessories with purposes of expanding usage. It complies with standards of IEC 157-1 & VDE0660,etc.

Specifications

Rated current of trip

(A)

0.16

0.25

0.40

0.63

1.0

1.6

2.5

4.0

6.3

10

16

Rated fixed current

(A)

0.1-

0.16

0.16-

0.25

0.25-0.40

0.40-0.63

0.63-1.0

1.0-1.6

1.6-

2.5

2.5-

4.0

4.0-

6.3

6.3-

10

9.5-

16

Code

05

09

13

17

21

25

29

33

37

42

46


3VE Motor Protection Circuit Breaker





3VE are suitable i n AC circuit of 50/60Hz, voltage up to 660V and current up o 0.1-16A and used to prevent small capacity motor and circuits from overload and short circuit and also used as direct starter for starting the motor and a switch for changeover the circuit under normal conditions.



Specifications

Type

3VE1

3VE3

3VE4

Poles

3

3

 

Rated current (A)

20

32

3

Rated Voltage (V)

660

660

63

Rated insulation voltage (V)

660V

750

75660

Current setting range (A)

0.1-0.16 0.16-0.25 0.25-0.4 0.4-0.63

0.63-1.1-1.6

1.6-2.5 2-3.2

2.5-4 3.2-5

4-6.3 5-8

6.3-10 8-12.5

10-16 14-20

1-1.6 1.6-2.5

2.5-4 4-6.3

6.3-10 8-12.5

10-16 12.5-20

16-25 22-32

6.3-10 10-16

16-25 22-32

28-40 36-50

45-63

Power of

controlled

motor (KW)

220V

5.5

9

18

380V

10

16

32

660V

13

26

58

Mechanical life

(1x106)

10

10

3

Protective

feature

220V

Not act within 2hrs

380V

Act within 2hrs

660V

Action snap

RDM7 (EA,SA) series Moulded Case Circuit Breaker

It is suitable for shipping and land ,in the circuit with AC 50 or 60Hz, rated insulation voltage 660V, DC voltage 250V or less, rated current from 3A to 1200A, used for making and breaking circuit unfrequently, and protecting circuit against over load short circuit.

SA Specifications


 








Type

Pole No.

Rated current (A)

Rated Voltage
(V)  AC

Breaking capacity (KA)

600

500

440

400

230

SA32B

2

3,5,10,15,20,30

690

----

1.5/1

2.5/1

5/2

5/2

SA33B

3

3,5,10,15,20,30

690

----

1.5/1

2.5/1

5/2

5/2

SA53B

3

10,15,20,30,40,50

690

2.5/1

5/3

7.5/4

7.5/4

10/5

SA54B

4

10,15,20,30,40,50

690

2.5/1

5/3

7.5/4

7.5/4

10/5

SA63B

3

60

690

2.5/1

5/3

7.5/4

7.5/4

10/5

SA103B

3

15,20,30,40,50,60,75,100

690

10/5

15/8

25/13

30/15

50/25

SA104B

4

15,20,30,40,50,60,75,100

690

10/5

15/8

25/13

30/15

50/25

SA203B

3

125,150,175, 200,225

690

15/8

18/19

25/13

30/15

50/25

 

SA403B

3

250,300,350,400

690

----

22/11

35/18

30/15

50/25




 

EA Specifications

Type

Pole No.

Rated current (A)

Rated Voltage
(V) AC

Breaking capacity (KA)

600

500

440

400

230

EA32B

2

3,5,10,15,20,30

500

----

----

1.5/1

1.5/1

2.5/1

EA33B

3

3,5,10,15,20,30

500

----

----

1.5/1

1.5/1

2.5/1

EA52B

2

5,10,15,20,30,40,50

690

----

1.5/1

2.5/1

5/2

5/2

EA53B

3

5,10,15,20,30,40,50

690

----

1.5/1

2.5/1

5/2

5/2

EA63B

3

60

690

----

1.5/1

2.5/1

5/2

5/2

EA102B

2

50,60,75,100

690

5/2

7.5/2

10/3

15/4

25/7

EA103B

3

50,60,75,100

690

5/2

7.5/2

10/3

15/4

25/7

EA103F

3

60,75,100

415

----

----

----

1.5/1

5/2

EA104B

4

50,60,75,100

690

5/2

7.5/5

10/7.5

15/10

25/10

EA203B

3

125,150,175, 200,225

690

----

10/3

15/4

18/5

30/18

EA403B

3

250,300,350,400

690

----

18/9

25/13

25/13

35/18

SA Outline Dimensions (mm)

Type

SA32B